Water cooling units
- Water cooling unit for shakers 74 kN to 300 kN
- Integrated is the complete primary circuit of the shaker cooling and the hydraulics for the hydrostatic guide bearings.
- The extraction of the heat is carried out by a customer-provided secondary-process water circuit
- Monitoring of all circuits by several pressure gauges and flow indicators
- Multifunctional display
- Connected to the shaker by hoses with self-sealing couplings that are free from leakage
- Closed primary circuit to prevent evaporation and pollution
- Integrated demineralisation and monitoring of conductance
- Reduced water consumption by controlling the process water flow
- Good accessibility by designing the front and side walls as swing doors
- Designed as compact mobile device
C 59412 (for water-cooled shakers with a nominal force of 74 kN to 125 kN)
Supply temperature: | 5-15 °C |
Volumeflow at max. supply temperature: | 10 m³/h |
Supply pressure –static: | less or equal to 800 kPa |
Hose connection – thread: | G 1 1/2" |
Dimensions WxHxD: | 800 x 2200 x 900 mm |
Total mass: | ~300 kg |
C 59430 (for water-cooled shakers with a nominal force of 130 kN to 300 kN)
Supply temperature: | 5-15 °C |
Volumeflow at max. supply temperature: | 15 m³/h |
Supply pressure –static: | less or equal to 800 kPa |
Hose connection – thread: | G 1 1/2" |
Dimensions WxHxD: | 800 x 2200 x 1100 mm |
Total mass: | ~500 kg |